Partly as a result of the use of 190 mm fans that revolve more slowly, Brink Climate Systems succeeded in further reducing the sound level. The reduction of the internal resistance of the appliance and heat exchanger contributes further to the noiseless operation of the Renovent Excellent. The connection diameter of the ducts has increased. In combination with the larger diameter air ducts, that reduces the airflow rate and so the sound.
Lower auxiliary energy consumption
An additional advantage of the measures to reduce the noise level is that they also reduce the auxiliary energy consumption. With the Renovent Excellent, Brink Climate Systems succeeded in introducing an appliance that amply complies with the future European requirements of a maximum of 1.200 J/m3. But already today you can benefit from a further EPC reduction.
Constant flow control
Application of constant flow control guarantees the preset airflow rates independent of the resistance in the ducts system. The guaranteed ventilation balance ensures that the high efficiency will be maintained under all conditions. The constant flow principle simplifies tuning and that saves installation costs. On top of that, the filter fouling degree no longer affects the flow rate of the clean outdoor air supply. A unique feature is that Brink Climate Systems manages to combine the constant flow principle with the ultimate low-noise and low-energy EC fans with patented back-bent vanes.
Frost protection
A frost protection system prevents the heat exchanger from freezing when it is very cold outside. In the Renovent Excellent this is a smart frost protection system with a preheater. Temperature sensors monitor the heat exchanger condition and only switch on the preheater when it is necessary. That guarantees high efficiency and the ventilation balance also under extremely low outdoor temperatures.
Excellent 300 | ||||||||||||||
Supply Voltage | 230V/50Hz | |||||||||||||
Dimensions (wxhxd) (mm) | 675 x 765 x 564 | |||||||||||||
Duct diameter (mm) | 160 | |||||||||||||
External diameter condensate discharge (mm) | 32 | |||||||||||||
Weight (kg) | 38 | |||||||||||||
Filter class | G3 (F7 optional for supply) | |||||||||||||
Fan Setting (factory setting) | 0 | 1 | 2 | 3 | max | |||||||||
Factory Setting (m3/hr) | 50 | 100 | 150 | 225 | 300 | |||||||||
Permissible resistance of duct system (Pa) | 3-76 | 11-28 | 26-66 | 56-142 | ||||||||||
Rated power (excl. preheater) (W) | 9.0-9.2 | 13.7-15.2 | 22.0-29.2 | 46.8-66.2 | ||||||||||
Rated current (excl. preheater) (A) | 0.104-0.107 | 0.150-0.161 | 0.214-0.274 | 0.403-0.578 | ||||||||||
Max. rated current (incl. preheater switched on) (A) | 6 | |||||||||||||
Cos | 0.368-0.374 | 0.391-0.416 | 0.447-0.463 | 0.505 | ||||||||||
Sound power | ||||||||||||||
(m3/h) | p (Pa) | Filter | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | Total Lw (dB) | Total weighed (dB(A)) | ||
90
|
50 | ISO Coarse 60% | 60.3 | 56.5 | 52.3 | 47.7 | 37.8 | 29.2 | 18.2 | 20.9 | 62.4 | 48.6 | ||
100 | ISO Coarse 60% | 59.4 | 62.1 | 54.4 | 50.5 | 41.6 | 34.7 | 22.5 | 21.4 | 64.6 | 51.8 | |||
150
|
50 | ISO Coarse 60% | 60.9 | 65.2 | 59.6 | 55.4 | 45.7 | 40.0 | 27.7 | 21.7 | 67.7 | 56.3 | ||
100 | ISO Coarse 60% | 61.4 | 61.1 | 62.1 | 59.7 | 48.1 | 42.7 | 31.2 | 23.3 | 67.2 | 59.0 | |||
210
|
50 | ISO Coarse 60% | 63.6 | 63.9 | 65.9 | 64.2 | 53.1 | 48.2 | 38.2 | 28.0 | 70.6 | 63.3 | ||
100 | ISO Coarse 60% | 63.7 | 63.9 | 66.9 | 63.1 | 53.8 | 49.0 | 39.2 | 29.5 | 70.8 | 63.1 | |||
300
|
50 | ISO Coarse 60% | 70.0 | 70.0 | 73.5 | 70.2 | 60.7 | 56.6 | 48.7 | 41.2 | 77.4 | 70.0 | ||
100 | ISO Coarse 60% | 69.1 | 68.8 | 71.2 | 70.0 | 60.8 | 56.7 | 48.8 | 42.0 | 76.1 | 69.3 | |||
Sound power | ||||||||||||||
(m3/h) | p (Pa) | Filter | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | Total Lw (dB) | Total weighed (dB(A)) | ||
90
|
50 | ISO Coarse 60% | 61.0 | 53.5 | 43.3 | 34.8 | 18.7 | 14.3 | 15.9 | 20.9 | 61.7 | 41.2 | ||
100 | ISO Coarse 60% | 59.5 | 47.1 | 44.9 | 36.7 | 21.6 | 17.7 | 16.0 | 20.9 | 59.9 | 40.1 | |||
150
|
50 | ISO Coarse 60% | 58.0 | 52.9 | 50.0 | 42.3 | 26.1 | 23.2 | 16.9 | 20.9 | 59.7 | 44.6 | ||
100 | ISO Coarse 60% | 60.7 | 60.8 | 54.3 | 44.8 | 28.1 | 25.1 | 17.2 | 20.8 | 64.3 | 49.3 | |||
210
|
50 | ISO Coarse 60% | 59.4 | 53.4 | 57.5 | 48.8 | 32.6 | 30.8 | 22.0 | 20.8 | 62.4 | 51.0 | ||
100 | ISO Coarse 60% | 63.7 | 57.1 | 58.5 | 49.5 | 33.3 | 31.5 | 21.7 | 21.0 | 65.6 | 52.1 | |||
300
|
50 | ISO Coarse 60% | 61.0 | 57.6 | 65.2 | 56.7 | 40.5 | 38.5 | 29.9 | 21.7 | 67.5 | 58.6 | ||
100 | ISO Coarse 60% | 63.6 | 58.1 | 64.5 | 56.9 | 41.1 | 39.2 | 31.9 | 22.1 | 68.0 | 58.3 | |||
Sound power | ||||||||||||||
(m3/h) | p (Pa) | Filter | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | Total Lw (dB) | Total weighed (dB(A)) | ||
90
|
50 | ISO Coarse 60% | 41.5 | 34.8 | 35.8 | 27.2 | 20.0 | 14.6 | 15.9 | 20.8 | 30.0 | |||
100 | ISO Coarse 60% | 41.6 | 40.4 | 37.3 | 30.2 | 23.9 | 16.8 | 15.9 | 20.6 | 33.0 | ||||
150
|
50 | ISO Coarse 60% | 39.6 | 47.5 | 41.6 | 33.8 | 25.2 | 20.8 | 16.5 | 20.8 | 38.0 | |||
100 | ISO Coarse 60% | 42.1 | 43.6 | 43.8 | 35.9 | 26.7 | 22.2 | 16.9 | 20.6 | 38.0 | ||||
210
|
50 | ISO Coarse 60% | 40.6 | 41.3 | 52.6 | 42.4 | 31.9 | 26.5 | 19.0 | 21.9 | 44.0 | |||
100 | ISO Coarse 60% | 41.7 | 42.3 | 54.7 | 43.8 | 33.2 | 27.8 | 20.3 | 21.2 | 46.0 | ||||
300
|
50 | ISO Coarse 60% | 42.7 | 48.8 | 56.0 | 48.0 | 39.1 | 37.0 | 30.6 | 26.5 | 50.0 | |||
100 | ISO Coarse 60% | 44.9 | 49.5 | 57.6 | 48.9 | 40.3 | 38.0 | 31.9 | 28.4 | 52.0 |