Brink Renovent Excellent 400

Heat Recovery Ventilation

The Brink Renovent Excellent 400 is a mechanical ventilation with heat recovery unit with an efficiency of 95%, low-energy fans and a maximum ventilation capacity of 400m3/h. The Brink Renovent Excellent 400 comes ready to plug in with a 230V mains plug and a connection for a low voltage multiple switch on the outside of the appliance.

Features of the Brink Renovent Excellent 400:

  • Adjustable airflow rates via control panel
  • Filter change indication
  • Frost protection
  • Summer by pass
  • Low energy consumption
  • High efficiency
  • Passive House Certified

Silent

Partly as a result of the use of 190 mm fans that revolve more slowly, Brink Climate Systems succeeded in further reducing the sound level. The reduction of the internal resistance of the appliance and heat exchanger contributes further to the noiseless operation of the Renovent Excellent. The connection diameter of the ducts has increased. In combination with the larger diameter air ducts, that reduces the airflow rate and so the sound.

Lower auxiliary energy consumption

An additional advantage of the measures to reduce the noise level is that they also reduce the auxiliary energy consumption. With the Renovent Excellent, Brink Climate Systems succeeded in introducing an appliance that amply complies with the future European requirements of a maximum of 1.200 J/m3. But already today you can benefit from a further EPC reduction.

Constant flow control

Application of constant flow control guarantees the preset airflow rates independent of the resistance in the ducts system. The guaranteed ventilation balance ensures that high efficiency will be maintained under all conditions. The constant flow principle simplifies tuning and that saves installation costs. On top of that, the filter fouling degree no longer affects the flow rate of the clean outdoor air supply. A unique feature is that Brink Climate Systems manages to combine the constant flow principle with the ultimate low-noise and low-energy EC fans with patented back-bent vanes.

Frost protection

A frost protection system prevents the heat exchanger from freezing when it is very cold outside. In the Renovent Excellent this is a smart frost protection system with preheater. Temperature sensors monitor the heat exchanger condition and only switch on the preheater when it is necessary. That guarantees the high efficiency and the ventilation balance also under extremely low outdoor temperatures.

Excellent 400
Supply Voltage 230V/50Hz
Dimensions (wxhxd) (mm) 675 x 765 x 564
Duct diameter (mm) 180
External diameter condensate discharge (mm) 32
Weight (kg) 38
Filter class G3 (F7 optional for supply)
Fan Setting (factory setting) 0 1 2 3 max
Factory Setting (m3/hr) 50 100 200 300 300
Permissible resistance of duct system (Pa) 3-6 6-20 25-49 56-178
Rated power (excl. preheater) (W) 8.6 9.5-15 29-40 72-98
Rated current (excl. preheater) (A) 0.10 0.12-0.14 0.24-0.31 0.51-0.70
Max. rated current (incl. preheater switched on) (A) 6
Cos 0.380 0.45-0.40 0.56-0.58 0.60-0.61
Sound power
(m3/h) p (Pa) Filter 63 125 250 500 1000 2000 4000 8000 Total Lw (dB) Total weighed (dB(A))
100
9 ISO Coarse 60% 59.1 56.9 49.4 45.1 35.2 29.4 16.9 9.5 61.5 46.6
40 ISO Coarse 60% 60.9 60.7 54.5 49.8 40.3 35.8 24.6 12.0 64.4 51.2
200
38 ISO Coarse 60% 65.6 64.5 64.2 59.2 50.1 47.5 38.0 25.0 70.0 60.0
80 ISO Coarse 60% 66.1 64.8 65.1 61.4 52.4 49.5 40.7 28.6 70.8 61.7
225
47 ISO Coarse 60% 67.3 66.7 67.0 62.6 53.9 51.4 43.3 30.7 72.3 63.2
100 ISO Coarse 60% 68.3 67.0 67.1 64.6 56.4 53.3 45.0 33.7 73.1 64.6
300
84 ISO Coarse 60% 71.4 70.4 71.5 67.7 59.9 57.8 50.1 39.6 76.6 68.3
175 ISO Coarse 60% 71.7 71.3 75.4 69.4 61.7 59.5 51.7 42.2 78.7 70.7
240 ISO Coarse 60% 72.1 72.4 71.6 70.5 62.7 60.9 53.0 44.3 77.9 70.5
400
150 ISO Coarse 60% 74.5 74.5 74.1 72.5 64.6 53.1 55.6 47.0 80.1 72.1
225 ISO Coarse 60% 74.5 74.7 73.0 74.0 65.9 64.2 56.6 48.5 80.4 73.6
Sound power
(m3/h) p (Pa) Filter 63 125 250 500 1000 2000 4000 8000 Total Lw (dB) Total weighed (dB(A))
100
9 ISO Coarse 60% 55.6 50.7 40.9 33.7 18.6 15.5 8.9 11.6 56.9 38.2
40 ISO Coarse 60% 55.1 47.0 45.0 37.2 20.9 16.7 9.4 8.4 56.1 39.5
200
38 ISO Coarse 60% 52.2 55.0 61.1 46.4 31.0 28.9 20.6 12.2 62.6 53.2
80 ISO Coarse 60% 57.0 52.3 62.4 48.2 32.8 30.2 22.5 8.6 63.9 54.4
225
47 ISO Coarse 60% 59.0 54.0 62.4 49.7 34.5 32.1 25.2 12.7 64.6 54.7
100 ISO Coarse 60% 59.1 53.7 61.8 51.2 36.4 33.6 26.6 11.5 64.3 54.5
300
84 ISO Coarse 60% 59.4 58.5 69.3 55.9 41.5 39.4 32.8 17.4 70.2 61.4
175 ISO Coarse 60% 62.9 59.8 66.5 57.8 42.8 40.8 34.1 19.2 69.0 59.8
240 ISO Coarse 60% 63.0 62.4 66.9 58.8 44.4 42.3 35.3 21.1 69.7 60.5
400
150 ISO Coarse 60% 64.4 63.8 68.4 61.6 46.6 45.2 38.4 23.9 71.3 62.5
225 ISO Coarse 60% 63.4 63.9 67.0 63.0 47.4 45.7 38.8 24.7 70.7 62.6
Sound power
(m3/h) p (Pa) Filter 63 125 250 500 1000 2000 4000 8000 Total Lw (dB) Total weighed (dB(A))
100
9 ISO Coarse 60% 37.3 30.7 30.4 31.1 20.0 10.4 4.8 7.1 29.5
40 ISO Coarse 60% 35.6 37.4 34.2 32.9 23.1 17.5 8.2 7.1 32.5
200
38 ISO Coarse 60% 41.9 40.5 48.0 38.5 29.8 27.7 20.3 12.5 40.5
80 ISO Coarse 60% 42.4 40.2 47.2 40.1 32.7 30.3 23.6 15.8 41.5
225
47 ISO Coarse 60% 42.2 41.4 49.8 41.9 33.2 31.3 25.5 17.5 43.5
100 ISO Coarse 60% 42.9 43.3 54.7 43.5 36.6 34.4 28.4 20.6 47.5
300
84 ISO Coarse 60% 45.2 46.6 56.1 49.1 40.2 39.0 34.2 28.3 51.0
175 ISO Coarse 60% 45.9 47.8 54.1 53.3 43.0 41.5 36.2 30.7 53.0
240 ISO Coarse 60% 49.9 48.2 56.0 51.9 45.5 44.4 39.0 33.7 54.0
400
150 ISO Coarse 60% 48.7 50.3 55.9 54.0 45.4 44.3 40.2 36.7 54.5
225 ISO Coarse 60% 52.6 50.9 57.2 58.9 47.4 46.3 41.7 38.2 57.0

More About The Brink Climate System

The Brink Renovent Excellent 400 is a mechanical ventilation with heat recovery unit with an efficiency of 95%, low-energy fans and a maximum ventilation capacity of 400m3/h. At CVC Direct we are happy to plan, deliver and install your complete ventilation project or heating recovery system. If you’d like more information about any of our systems for home ventilation our highly qualified team are here to help.